Overview

The Cleaver Brooks CBLE model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. The CBLE is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower. The LE identifier means that this boiler is designed and built to operate with low emissions while maintaining the high fuel to steam efficiency that Cleaver Brooks boilers are known for.

This boiler was purchased by Powerhouse from a customer who was replacing these boilers with new ones. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

  • BrandCleaver Brooks
  • Boiler TypeFiretube
  • Output Capacity2,415 - 24150 PPH
  • Max Pressure50 - 150 PSIG
  • Fuel(s)#2 Oil, Natural Gas
  • ServiceSaturated Steam
  • Emission Rating20 ppm

Technical Specifications

General Design

  • Manufacturer (OEM)Cleaver-Brooks
  • Year 1998
  • Serial No.OL097980
  • National Board No.9460
  • CRN No.-
  • ModelCB-200-700-150
  • TypeScotch
  • DesignFour-Pass Dry Back Firetube
  • MountingSaddles & Skid-Mounted
  • InternalCorrugated Furnace & Straight Tubes

Capacities & Inputs

  • Output Capacity24,150 LBS/HR
  • Horsepower700 BHP
  • Design Pressure (MAWP)150 PSIG
  • Operating Range50-140 PSIG
  • Heating Surface3,500 FT²
  • Max. Fuel InputNG: 28,576,200 BTU/HR #2: 204.1 GPH
  • Standard FuelsNatural Gas & #2 Fuel Oil
  • Additional Fuels#6 Fuel Oil
  • Input Gas PressureMin: 2.24 PSIG
  • Turndown RatiosNG: 10:1 #2: 8:1
  • Emission Rating (NOX)NG: 20 PPM #2: 90 PPM

Burner and Electrical

  • Burner Manufacturer (OEM)Cleaver-Brooks
  • ModelLE
  • TypeFull Modulation
  • Flue Gas Recirculation (FGR)Yes, 18%
  • Electric460V/3PH/60Hz
  • AtomizationAir
  • Control TypeSingle Point Positioning
  • Boiler Control System-
  • Burner Management SystemHoneywell RM7800
  • Flame SafeguardIR Scanner
  • Blow Motor75 HP
  • Burner Installed Yes
  • Pilot TypeYes / Spark
  • Instrument Air-
  • Air CompressorIncluded (7.5 HP)

Dimensions and Weights

  • Overall Length25' 5-5/8"
  • Overall Height11' 2"
  • Overall Width9' 7"
  • Shipping Weight52,050 LBS
  • Operating Weight75,050 LBS
  • Boiler Outlet8" ø 300# FLG.
  • Exhaust Outlet24" ø OD

Technical Overview PDF

Download PDF