Overview

The Cleaver Brooks CBLE model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. The CBLE is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower. The LE identifier means that this boiler is designed and built to operate with low emissions while maintaining the high fuel to steam efficiency that Cleaver Brooks boilers are known for.

This boiler was purchased brand new from Cleaver Brooks in 2008 and served in our rental fleet. It has since been removed from it's rental stage, fully reconditioned, and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

  • BrandCleaver Brooks
  • Boiler TypeFiretube
  • Output Capacity1,208 - 12,075 PPH
  • Max Pressure80 - 200 PSIG
  • Fuel(s)#2 Oil, Natural Gas, Propane
  • ServiceSaturated Steam
  • Emission Rating30 ppm

Technical Specifications

General Design

  • Manufacturer (OEM)Cleaver-Brooks
  • Year2008
  • Serial No.OL106838
  • National Board No.15580
  • CRN No.L1038.5
  • ModelCBLE-200-350-200
  • TypeScotch
  • DesignFour-Pass Dryback Firetube
  • MountingSaddles & Skid-Mounted
  • InternalCorrugated Furnace & Straight Tubes

Capacities & Inputs

  • Output Capacity12,075 LB/HR
  • Horsepower350 BHP
  • Design Pressure (MAWP)200 PSIG
  • Operating Pressure Range50 - 185 PSIG
  • Heating Surface1,750 FT²
  • Max. Fuel InputNG: 14,288,00 BTU/HR #2: 102.1 GAL/HR
  • Standard FuelsNatural Gas & #2 Fuel Oil
  • Additional Fuels#6 Fuel Oil
  • Input Gas PressureMAX: 4.5 PSIG MIN: 45 " WC
  • Turndown RatiosNG: 10:1 #2: 8:1
  • Emission Rating (NOX)NG: 30 PPM #2: 90 PPM

Burner and Electrical

  • Burner Manufacturer (OEM)Cleaver-Brooks
  • ModelIntegral - LE
  • TypeFull Modulation
  • Flue Gas Recirculation (FGR)Yes
  • Electric480V/3Ph/60Hz
  • AtomizationAir
  • Control TypeSingle-Point Positioning
  • Boiler Control System-
  • Burner Management SystemHoneywell RM7800L
  • Flame SafeguardIR Scanner
  • Blow Motor30 HP
  • Burner Installedyes
  • Pilot TypePropane (LPG), NG, Spark
  • Instrument Air-
  • Air Compressor5HP (Included)

Dimensions and Weights

  • Overall Length20' 10"
  • Overall Height9' 7"
  • Overall Width8' 0"
  • Shipping Weight29,300 LBS
  • Operating Weight44,765 LBS
  • Boiler Outlet6" ø 300# Studdery FLG.
  • Exhaust Outlet20" ø OD

Technical Overview PDF

Download PDF