Overview

The Cleaver Brooks CB model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. This CB is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower.

This boiler was purchased by Powerhouse from a customer who was replacing these boilers with new ones. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

  • BrandCleaver Brooks
  • Boiler TypeFiretube
  • Output Capacity2,415 - 24,150 PPH
  • Max Pressure90 - 150 PSIG
  • Fuel(s)#2 Oil, Natural Gas
  • ServiceSaturated Steam
  • Emission RatingUncontrolled

Technical Specifications

General Design

  • Manufacturer (OEM)Cleaver-Brooks
  • Year1995
  • Serial No.L-93860
  • National Board No.4303
  • CRN No.-
  • ModelCB-200-700-150
  • ASME CodeSect I - High Pressure Steam
  • TypeScotch
  • DesignFour-Pass Dry Back Firetube
  • MountingLegs & Skid-Mounted
  • InternalCorrugated Furnace & Straight Tubes

Capacities & Inputs

  • Output Capacity24,150 LB/HR
  • Horsepower700 BHP
  • Design Pressure (MAWP)150 PSIG
  • Operating Range90 -135 PSIG
  • Heating Surface3,500 FT²
  • Max. Fuel InputNG: 29,291,000 BTU/HR #2: 209 GAL/HR
  • Standard FuelsNatural Gas & #2 Fuel Oil
  • Additional Fuels-
  • Input Gas PressureMin: 21. PSIG
  • Turndown RatiosNG: 10:1 #2: 8:1
  • Emission Rating (NOX)Uncontrolled (~100 PPM)

Burner and Electrical

  • Burner Manufacturer (OEM)Cleaver-Brooks
  • ModelIntegral
  • TypeFull Modulation
  • Flue Gas Recirculation (FGR)No
  • Electric460V/3PH/60Hz
  • AtomizationAir
  • Control TypeSingle Point Positioning
  • Boiler Control System-
  • Burner Management SystemHoneywell RM7800
  • Flame SafeguardIR Scanner
  • Blow Motor40 HP
  • Burner InstalledYes
  • Pilot TypeInterrupted Gas / Spark Ignited
  • Instrument AirOil Atomization
  • Air Compressor7.5 HP (Included)

Dimensions and Weights

  • Overall Length26' 5"
  • Overall Height10' 6"
  • Overall Width11' 0"
  • Shipping Weight53,300 LBS
  • Operating Weight81,030 LBS
  • Boiler Outlet8" ø 300# FLG.
  • Exhaust Outlet24" ø OD

Technical Overview PDF

Download PDF