Overview

The Cleaver Brooks CB model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. This CB is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower.

This boiler was purchased new from Cleaver Brooks by Powerhouse and placed into a custom design portable boiler room for sale. After many years of reliable service the boilers were purchased back by Powerhouse. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

  • BrandCleaver Brooks
  • Boiler TypeFiretube
  • Output Capacity863 - 3,450 PPH
  • Max Pressure45 - 150 PSIG
  • Fuel(s)#2 Oil, Natural Gas
  • ServiceSaturated Steam
  • Emission RatingUncontrolled

Technical Specifications

General Design

  • Manufacturer (OEM)Cleaver-Brooks
  • Year2003
  • Serial No. L103223
  • National Brand No.8133
  • CRN No.-
  • ModelCB-200-100-150
  • TypeScotch
  • DesignFour-Pass Dry Back Firetube
  • MountingSaddles & Skid-Mounted
  • InternalStraight Furnace & Straight Tubes

Capacities and Inputs

  • Output Capacity3,450 LB/HR
  • Horsepower100 BHP
  • Design Pressure (MAWP)150 PSIG
  • Operating Range30 - 140 PSIG
  • Heating Surface500 FT²
  • Max. Fuel InputNG: 4,184,000 BTU/HR #2: 30.0 GAL/HR
  • Standard FuelsNatural Gas & #2 Fuel Oil
  • Additional Fuels#6 Fuel Oil
  • Input Gas Pressure11"WC Minimum
  • Turndown RatiosNG: 10:1 #2: 8:1
  • Emission Rating (NOX)Uncontrolled Emissions

Burner and Electrical

  • Burner Manufacturer (OEM) Cleaver-Brooks
  • ModelIntegral
  • TypeFull Modulation
  • Flue Gas Recirculation (FGR)No
  • Electric208V/3Ph/60Hz
  • AtomizationAir
  • Control Type Single-Point Positioning
  • Boiler Control System-
  • Burner Management SystemCleaver-Brooks CB780
  • Flame SafeguardIR Scanner
  • Blow Motor 3 HP
  • Burner InstalledYes
  • Pilot TypeNatural Gas/Spark
  • Instrument Air-
  • Air Compressor2 HP

Dimensions and Weights

  • Overall Length15' 8"
  • Overall Height6'7"
  • Overall Width5'6"
  • Shipping Weight9,500 lbs
  • Operating Weight14,588 lbs
  • Boiler Outlet4" ø 300# FLG.
  • Exhaust Outlet12" ø OD

Technical Overview PDF

Download PDF

Talk Boilers To Us