Overview

The Victory Voyager series is an O-Type watertube boiler which are large capacity boilers providing rapid ramp up rates for quick output and industrial performance for the harshest conditions. This boiler is constructed to ASME Section I code for saturated steam and comes with a Faber Burner capable of producing 82,500 PPH of steam up to 399 PSIG.

This boiler was purchased brand new from Victory in 2019 with a new Faber Burner and will soon join the rental fleet. Due to our strict processes and constant maintenance, this boiler will be kept in excellent condition for both rental and sale.

Specs

  • BrandVictory Energy
  • Boiler TypeWater tube
  • Output Capacity8,250 - 82,500 PPH
  • Max Pressure100 - 399 PSIG
  • Fuel(s)#2 Oil, Natural Gas
  • ServiceSaturated Steam
  • Emission Rating30 ppm

Technical Specifications

General Design

  • Manufacturer (OEM)Victory
  • Year2019
  • Serial No.TBD
  • National Board No.TBD
  • CRN No.TBD
  • ModelVSM-75-75SP
  • TypeWatertube
  • DesignO-Type
  • MountingIntegral Rail Mounted
  • InternalRefractory-Free Welded Membrane Side Walls & Pyro-blocks Front and Rear Walls

Capacities and Inputs

  • Output Capacity82,500 LB/HR
  • Horsepower2,391 BHP
  • Design Pressure (MAWP) & TEMP399 PSIG
  • Operating Pressure Range150 - 385 PSIG
  • Heating Surface5,615 FT²
  • Max. Fuel InputNG: 99,380,000 #2: 95,810,000
  • Standard FuelsNatural Gas & #2 Fuel Oil
  • Additional Fuels-
  • Input Gas PressureMAX: 25 PSIG MIN: 10 PSIG
  • Turndown RatiosNG: 10:1 #2: 8:1
  • Emission Rating (NOX)NG: 30 PPM Nox @ 3% O2 (Corrected) #2: 90 PPM NOx@ 3% O2 (Corrected)

Burner and Electrical

  • Burner Manufacturer (OEM)Faber
  • ModelWB-1-31-IFGR
  • TypeNG: Ring & Spud Oil: Gun
  • Flue Gas Recirculation (FGR)Yes, 15%
  • Electric480V/3Ph/60Hz
  • AtomizationAir/Steam
  • Control TypeSingle-Point
  • Boiler Control SystemPowerhouse BoilerLink®
  • Burner Management SystemHoneywell RM7800
  • Flame SafeguardUV Scanner
  • Blow Motor125 HP TEFC
  • Burner InstalledYes
  • Pilot Type Natural Gas
  • Instrument Air150 SCFM @ 100 PSIG
  • Air CompressorRequired - Available at Additional Cost

Dimensions and Weights

  • Overall Length37' 2-1/4"
  • Overall Height18' 5" (20' 4" w/Economizer)
  • Overall Width10' 9-1/2"
  • Shipping Weight81,000 LBS
  • Operating Weight100,000 LBS
  • Boiler Outlet 10" 300# FLG.
  • Exhaust Outlet6' 0" x 4' 11-5/16"
  • Stub Stack Outlet42" ø ID

Technical Overview PDF

Download PDF

Talk Boilers To Us